Design case study · Melbourne inner east

Hydronic heating case study: a Melbourne heritage home with a modern extension

This hydronic heating case study works through a typical Melbourne heritage home in the inner east — a double-brick Victorian or Edwardian front with a modern rear extension — and shows how we combine a Maxa i-290 R290 heat pump, in-slab underfloor heating in the extension, ThermaSkirt skirting-board heating in the period rooms and a Viessmann Vitocal 161-A for hot water, so every zone gets the emitter it suits without lifting an original floorboard.

About this case studyThis design case study shows how we specify and integrate a multi-brand system for a typical heritage home with a modern extension. Figures are design-stage calculations and manufacturer data for a home of this type — not measured results from a single named property.
Documented by AHHAC Technical Team · 30 October 2026
~13.4 kW
Design-day heat loss at −1 °C (worked example)
16 kW
Maxa i-290 selected (design)
35–40 °C
Underfloor flow via mixing valve (design)
0
Original floorboards lifted (design intent)
Authorised supplier & installer
Maxa authorised supplierViessmann authorised installerImmergasSimeThermaSkirt™
Plumbing Lic 262528CABN 85 164 746 4906 showrooms · NSW · ACT · VIC · QLDEst. 1998

The brief: what a Melbourne heritage home with an extension needs

It's a pattern that runs right through Melbourne's inner east, from hydronic heating in Kew to Camberwell: a Victorian or Edwardian house with high ceilings, ornate cornices and original timber floors at the front, and a contemporary open-plan kitchen, living and dining extension at the back, usually on a new concrete slab with a wall of glass facing the garden. The two halves of the house behave like two different buildings, and that is the whole design problem.

For this worked example we've assumed:

  • About 230 m² heated — 105 m² of heritage front (entrance hall, front sitting room, three bedrooms, original bathroom) and 125 m² of rear extension (open-plan kitchen/living/dining, ensuite, laundry and mudroom).
  • Heritage front: double brick, ceilings around 3.3 m, single-glazed timber sashes, suspended timber floors over an accessible subfloor, with ceiling insulation topped up as part of the renovation.
  • Extension: new slab, built to current energy standards, double-glazed, with large north- and west-facing glazing.
  • Household: four people, two bathrooms, an all-electric goal and rooftop solar installed or planned.
  • Climate: Melbourne's −1 °C design temperature and roughly 1,500 heating degree-days a year.

The goals we hear from owners of homes like this are consistent: warm every room, including the cold front bedrooms; no bulkheads, ducts or visible plant at the front of the house; nothing that harms original floors, cornices, ceiling roses or lath-and-plaster walls; some cooling for the glazed extension, which overheats on summer afternoons; get off gas with low running costs; and quiet outdoor plant that won't upset the neighbours on a tight inner-suburban block.

Why one brand wasn't enough

No single product does all of that well. A one-emitter system forces a compromise somewhere — radiators on every wall of an extension that is mostly glass and joinery, or underfloor heating that can't go into the heritage rooms without lifting the boards. So we pick the right tool for each zone and make the pieces work as one hydraulic system, designed and installed by our own licensed plumbers and hydronic engineers rather than subcontractors.

Maxa i-290 — the heat source for heating and cooling

The Maxa i-290 is a sealed R290 monoblock: the refrigerant stays inside the outdoor unit and only water pipes enter the house. It heats and cools, carries a published heating COP of 4.94 on the 16 kW model, and comes in three chassis covering 6–27 kW, so we can match it closely to the calculated load. Because it can deliver water up to 78 °C, it has comfortable headroom to run the warmer ThermaSkirt circuit as well as the cooler underfloor one.

In-slab underfloor — the extension

The extension slab is being poured anyway, so running the Maxa heat pump into hydronic underfloor heating there adds little to the floor build and uses no wall space. At a 35–40 °C flow it keeps the heat pump in its most efficient band, warms a large glazed room evenly from the ground up, and can carry gently chilled water in summer.

ThermaSkirt — the heritage rooms

ThermaSkirt replaces the ordinary skirting board with a 22 mm-deep, 150 mm-high aluminium profile carrying integrated 12 mm hydronic pipework, turning the whole perimeter of the room into a low-temperature emitter. The pipes reach it from the subfloor, so original floors stay down and walls are not chased. Our ThermaSkirt vs radiators vs underfloor heating guide compares the three emitters in more depth.

IMAS radiators and towel warmers — the gaps

IMAS radiators fill the two places the other emitters can't: Alubain aluminium towel warmers in both bathrooms, and a single IMAS Klassic column radiator in the front sitting room's bay window, where — as the numbers below show — the skirting run alone can't carry the load at the flow temperature we want.

Viessmann Vitocal 161-A — domestic hot water

Hot water comes from a separate Viessmann Vitocal 161-A, an R290 heat pump water heater with an integrated tank (200 L or 270 L; we've assumed 270 L for a family of four with two bathrooms). Viessmann rates it at COP 4.15 (A20/15, W15/55 °C) with an operating range of −15 °C to 43 °C. Why it is separate is explained under design decisions.

MAXA thermostats — one controls layer

Each zone gets a MAXA thermostat — the Airmust P touch-screen or the simpler CRA wall thermostat — linked to the My House Pro app for schedules and remote control. We confirm compatibility with the manifold actuators at design stage.

ThermaSkirt skirting-board heating profile (product image)
ThermaSkirt profile · product image
Maxa i-290 R290 monoblock heat pump (product image)
Maxa i-290 heat pump · product image
IMAS Alubain aluminium towel warmer (product image)
IMAS Alubain towel warmer · product image
Viessmann Vitocal 161-A heat pump water heater (product image)
Viessmann Vitocal 161-A · product image

The system, zone by zone

Described in words, the schematic is simple — the skill is in the temperatures and the controls:

  1. Outdoor: the Maxa i-290 sits on a raised stand at the rear of the extension. Insulated flow and return pipes run into a plant cupboard in the laundry.
  2. Buffer tank: the heat pump charges a buffer tank, which acts as the hydraulic break between the heat pump and the two heating circuits.
  3. Circuit A — direct, warmer: water at the heat pump's flow temperature (about 50 °C on the design day, less on milder days) goes via a manifold in a cupboard (not a period room) to the ThermaSkirt runs, the IMAS Klassic radiator and both towel warmers. Pipework runs through the heritage subfloor, insulated along its length.
  4. Circuit B — mixed, cooler: a motorised mixing valve and its own circulator blend return water in to hold 35–40 °C, feeding the underfloor manifold in the extension. A high-limit protects the slab.
  5. Hot water: entirely separate. The Vitocal 161-A heats its own tank, with tempered water to the bathrooms and kitchen.
  6. Controls: each MAXA thermostat opens its zone actuator; the heat pump runs on a weather-compensation curve and responds to the buffer, not to individual rooms.
ZoneEmitterDesign flow tempControl
Kitchen / living / dining (extension)In-slab hydronic underfloor35–40 °C (mixed)MAXA wall thermostat; slab scheduled ahead of occupancy
Laundry and mudroom (extension)In-slab underfloor loops35–40 °C (mixed)Grouped with the living zone
Ensuite (extension)Underfloor + IMAS Alubain towel warmerFloor 35–40 °C; towel warmer ~50 °CMAXA thermostat; towel warmer on its own timer
Front sitting room (heritage)ThermaSkirt + one IMAS Klassic column radiator in the bay~45–50 °C (direct)MAXA wall thermostat
Bedrooms 1–3 (heritage)ThermaSkirt perimeter~45–50 °C (direct)MAXA thermostat per bedroom
Entrance hall (heritage)ThermaSkirt, unless the original skirting is retained~45–50 °C (direct)Grouped with the sitting room
Main bathroom (heritage)IMAS Alubain towel warmer~45–50 °C (direct)Own timer and valve
Summer coolingChilled water to the extension floor (optional MAXA fan coil)Held above dew pointDew-point sensor + living-zone thermostat
Domestic hot waterViessmann Vitocal 161-A, 270 L (separate)Stored hot, tempered at outletsBuilt-in Wi-Fi timer + app

Design decisions

1. Heat loss first, then sizing

Every AHHAC system starts with a room-by-room heat-loss calculation, and here the two halves of the house diverge. With the assumptions above, we've used about 70 W/m² for the heritage front at −1 °C (tall ceilings, single-glazed sashes, solid but uninsulated brick walls) and about 48 W/m² for the extension (insulated, double-glazed, but with a lot of glass). That gives roughly 7.4 kW for the front and 6.0 kW for the back — about 13.4 kW on the design day. We select the 16 kW i-290: enough margin to cover defrost cycles and recovery from a night setback without being so oversized that it short-cycles on mild days. On a real home these per-square-metre figures are replaced by the calculation itself.

2. One heat pump, two flow temperatures

This is the decision that makes or breaks a mixed-emitter system. Underfloor wants 35–45 °C; ThermaSkirt is designed around 45–55 °C. Run everything at 35 °C and the heritage rooms fall short. Run everything at 55 °C and the slab overheats while the heat pump's efficiency drops, because every degree of flow temperature costs COP. So the heat pump makes the warmer water for Circuit A, and the mixing valve on Circuit B blends it down for the floor. The heat pump runs on a weather-compensation curve, so on a 10 °C day it makes noticeably cooler water than on a frosty morning — and runs more efficiently for it.

3. Check every skirting run — and don't chase the last 5 °C

ThermaSkirt's output is set by the length of skirting in the room. We've used about 80 W/m, the middle of the published 70–90 W/m range, for a flow near 50 °C. A 3.6 × 4.0 m bedroom needs roughly 1.0 kW; after the door and wardrobe it has about 12.7 m of skirting, which gives about 1.0 kW. Covered. The front sitting room, about 24.5 m² with its bay, needs roughly 1.7 kW, but after the doorway, fireplace hearth and built-in joinery only about 16 m of skirting remains — about 1.3 kW. We could close the 0.4 kW gap by running the whole heritage circuit 5 °C hotter all winter, which would drag down the efficiency of the entire system. Adding one IMAS Klassic column radiator in the bay, sized for the same 50 °C flow, is the far better trade.

4. The buffer tank

With six thermostat zones and two towel warmers, there will be times when only one bedroom is calling for heat — far less than the heat pump's minimum output. Without a buffer, the compressor would start and stop repeatedly, wearing itself out and wasting energy. The buffer gives it a steady load, separates the heat-pump flow from the two secondary circuits so the mixing valve can do its job, and carries the low-mass ThermaSkirt rooms through defrost cycles so they don't go lukewarm on a frosty morning. We size it to the heat pump's minimum run time and the smallest zone that can call on its own.

5. Outdoor unit siting and noise

Inner-east blocks are tight, and the outdoor unit is the one part of the system the neighbours will notice. We place it at the rear of the extension, never at the front of a heritage streetscape, on a raised stand with anti-vibration mounts so defrost meltwater drains away from paths. We follow Maxa's clearance rules for an R290 unit around openings, drains and ignition sources, keep it off bedroom-window walls — ours and the neighbour's — and away from the boundary, and leave room for airflow and service access. The external pipework is insulated and frost-protected, and switchboard capacity is checked before quoting.

6. Hot water: why a separate Vitocal 161-A

The i-290 can make domestic hot water, and on some homes we let it. Here we don't, for four reasons. First, on a Melbourne winter morning the shower peak and the heating peak arrive together; with hot-water priority the heating circuits pause while the cylinder reheats, and the ThermaSkirt rooms feel it. Second, separating the loads lets us size the i-290 to the heating load alone rather than heating plus cylinder recovery. Third, two independent systems mean a service visit or fault on one never takes out both heat and hot water. Fourth, the Vitocal 161-A has its own Wi-Fi timer to run in solar hours, and as a registered heat pump water heater it is STC-eligible, which an air-to-water heat pump used for space heating is not — see our heat pump rebates guide. The trade-off is a second unit to find space for and service.

7. Heritage constraints

Original floors stay down: pipe runs go through the subfloor and come up at the skirting line, hidden behind the ThermaSkirt profile. Lath-and-plaster walls are not chased, there are no ceiling ducts or bulkheads, and cornices and ceiling roses are untouched. One honest caveat: ThermaSkirt replaces the skirting board itself, so it is the one piece of fabric the system touches. We remove original skirtings carefully, label them and store them on site so the change is reversible. Where a room's skirting is a significant decorative feature — often the entrance hall — we leave it in place and heat that room another way. If the property sits under a heritage overlay, we flag early that the owners or their designer should confirm with council whether anything visible needs approval.

8. Summer cooling without new plant

In summer the i-290 reverses and sends chilled water through the extension's floor loops, with a dew-point sensor that lifts the water temperature as humidity rises so the floor never sweats — the approach covered in our underfloor cooling article. ThermaSkirt and towel-warmer circuits are valved off in cooling mode. Floor cooling takes the edge off a west-facing glazed room rather than air-conditioning it, so where owners want more, a MAXA hydronic fan coil on the same chilled-water circuit adds capacity and dehumidification. The thick-walled front rooms are not cooled in this design.

Install sequence

The order matters as much as the equipment, because in most renovations of this kind the family is living in part of the house throughout.

  1. Survey and design. Room-by-room heat-loss calculation; record skirting profiles, subfloor access, switchboard capacity and the outdoor-unit position. Fixed-fee design and quote back within 24 hours of the site visit.
  2. Extension slab. Insulation and PEX-A loops laid and pressure-tested before the pour, with manifold positions and the plant pipe route set out with the builder. If the slab is already in, a 30–35 mm in-screed system goes on top instead.
  3. Plant. The i-290 on its stand, the buffer tank and mixing set in the laundry, the Vitocal 161-A in its position, and the electrical work.
  4. Heritage rooms, two at a time. Subfloor pipe runs go in first, from below, with no disruption above. Then skirting removal and ThermaSkirt fit-out room by room. Ideally this stage starts once the extension is habitable, so the household can live at the back while the front rooms are done.
  5. Bathrooms and the bay. Towel warmers after tiling, and the IMAS Klassic in the sitting-room bay.
  6. Fill and test. Fill, flush, inhibitor dose and pressure test, then commissioning.

Any existing heating in the front rooms stays in service until the new system is commissioned, and dusty work is sheeted off and kept to the room in hand. All plumbing is installed to AS/NZS 3500.

Commissioning and handover

  • Balancing: flow set on each underfloor loop at the manifold, and each ThermaSkirt circuit balanced so the bedroom furthest from the manifold gets its share.
  • Temperatures: the weather-compensation curve set so Circuit A sits near 50 °C at −1 °C and drops on milder days; the maximum flow on the mixed underfloor circuit locked in. A new slab is brought up to temperature gradually on first heat, not in one hit.
  • Defrost and cooling checks: confirm the buffer carries the heritage rooms through a defrost cycle; test the dew-point sensor and confirm the ThermaSkirt circuits close in cooling mode.
  • Controls: each MAXA thermostat paired with its zone, schedules set, the My House Pro app account enabled and the owners shown how to use it. Warranty is registered with MAXA at the same time.
  • Hot water: the Vitocal 161-A timer set to solar hours where there is rooftop PV, and its app connected.
  • Handover pack: heat-loss report, zone schedule, settings record, compliance certificates and warranty details — 7 years for the i-290 in domestic use and 5 years parts and labour on the Vitocal 161-A, as listed on our product pages.

We'd recommend reviewing the compensation curve after the home's first real cold spell, since that is when you learn whether a setting can come down a degree or two.

Expected performance and running cost (design stage)

These are design-stage numbers for a home matching the assumptions above. A real home's figures come from its own heat-loss calculation and, after a winter, its meter.

ItemDesign-stage figureHow we got there
Design-day heat loss~13.4 kWAssumed W/m² for each half of the house at −1 °C
Heat pumpMaxa i-290, 16 kWLoad plus defrost and recovery margin, within the 6–27 kW range
Seasonal heat demand~16,000 kWhDegree-day estimate of ~23,000 kWh if every room were held at temperature around the clock, × ~70% for zoning and setbacks
Seasonal COP assumed3.5–4.5 (4.0 central)Within the typical 3.5–5.5 band for heat pumps; below the 4.94 rated figure because of the ~50 °C circuit
Heating electricity~3,600–4,600 kWhHeat demand ÷ COP; ~4,000 kWh central
Hot waterUp to 70% less energyViessmann figure for the Vitocal 161-A vs a traditional electric storage heater

To turn that into dollars, multiply about 4,000 kWh by your own tariff: each 10 c/kWh adds or removes about $400 a heating season, before any solar offset. Heat pump running costs are typically 60–75% lower than gas for the same heat, which is why the all-electric route makes sense here. Comfort-wise, the low-mass ThermaSkirt and radiator circuit responds quickly — radiators typically warm a room in 15–25 minutes — while the slab in the extension responds over hours and is best left on a steady schedule. For the wider picture, see our hydronic heating running costs guide and our heat pump hydronic heating Melbourne page.

Would we do anything differently — and when this design doesn't fit

Looking over this design, three things deserve the hardest scrutiny on a real home. Envelope work comes first: ceiling insulation, draught-sealing the sashes and blocking unused chimneys cut the heritage load, and every watt saved lets ThermaSkirt run cooler. Fix the outdoor-unit position before the extension plans are final, so the pad, drainage and pipe route are drawn in rather than squeezed in. And keep the slab zones few: a slab responds over hours, so one well-scheduled living zone beats several thermostats fighting each other.

This design is the wrong answer when:

  • The front rooms are very large and leaky with little usable skirting — IMAS column or panel radiators carry more heat per metre of wall. See hydronic radiators in Melbourne.
  • The original skirtings are significant decorative fabric throughout — radiators are the more reversible choice.
  • There is nowhere for a second hot-water unit — let the i-290 heat an indirect cylinder and schedule reheats outside the morning heating peak.
  • Budget is the main constraint — a single-circuit i-290 and radiator system, in the $12,000–$30,000 range for radiator systems, is simpler and cheaper.
  • The owners want to keep gas — a Viessmann Vitodens 100-W condensing boiler can drive the same emitters, but gives up cooling and the heat pump's running-cost advantage.

For a heritage home with no extension at all, our heritage Sydney ThermaSkirt case study shows the skirting-only approach, and our hydronic heating Melbourne page covers every system we install across the city.

Common questions

Heritage home hydronic heating: FAQs

Can you install hydronic heating in a heritage home without lifting the floors?+
Yes, in most cases. In this design the heritage rooms are heated with ThermaSkirt, which replaces the skirting board, and the pipes reach it through the subfloor, so no original boards are lifted and no walls are chased. Where the subfloor can't be reached, or a room needs more heat than its perimeter allows, we add a period-style IMAS column radiator instead.
Can one heat pump run underfloor heating and ThermaSkirt at the same time?+
Yes. The Maxa i-290 feeds a buffer tank and two circuits draw from it: a direct circuit at around 45–50 °C for ThermaSkirt, radiators and towel warmers, and a mixed circuit where a mixing valve drops the water to 35–40 °C for the underfloor. Each circuit gets the temperature its emitters need, and the slab never sees the higher flow.
Why use a Viessmann Vitocal 161-A for hot water instead of the Maxa i-290?+
The i-290 can make hot water, but on a Melbourne winter morning the shower peak and the heating peak arrive together, and hot-water priority would pause the heating. A separate Vitocal 161-A keeps both running, lets the i-290 be sized to the heating load alone, and as a registered heat pump water heater it can attract STCs. Where there is no room for it, the i-290 with a cylinder is a sound fallback.
What size Maxa heat pump does a Melbourne heritage home with an extension need?+
It depends on the room-by-room heat-loss calculation. In this worked example — about 230 m², a double-brick front and a modern rear extension at Melbourne's −1 °C design temperature — the design-day load is about 13.4 kW, so we select the 16 kW i-290. The range runs from 6 to 27 kW, so a larger or leakier home may need the next size up.
Will ThermaSkirt alone heat a high-ceilinged Victorian room?+
Often, but not always. ThermaSkirt's output is limited by the length of skirting in the room — roughly 70–90 W per metre across its 45–55 °C flow range. Small bedrooms usually have enough perimeter; large sitting rooms with bay windows, fireplaces and built-in joinery often fall short. We check every room and add a column radiator where the run can't meet the load at an efficient flow temperature.
Can this hydronic system cool the house in summer?+
Partly. The i-290 reverses to send chilled water through the extension's floor loops, with a dew-point sensor that raises the water temperature as humidity rises so the floor never sweats. That takes the edge off a glazed living area. For stronger cooling we add a MAXA hydronic fan coil. ThermaSkirt circuits are closed off in cooling mode, and the heritage rooms are not cooled in this design.
Are there rebates for a heat pump hydronic system in Victoria?+
Only for part of it. The Vitocal 161-A, as a registered heat pump water heater, can attract STCs. Air-to-water heat pumps used for hydronic space heating, like the i-290 in this role, don't, and Victorian Energy Upgrades heating incentives cover air-to-air reverse-cycle units rather than hydronic heat pumps. Our heat pump rebates guide covers the detail.
How much does a multi-brand hydronic system like this cost?+
Whole-home hydronic systems typically run from $20,000 to $60,000+ installed. A design like this one — two heating circuits, a buffer tank, ThermaSkirt in the period rooms, underfloor in the extension and a separate hot-water heat pump — sits toward the upper part of that range. We provide a fixed-fee design and quote within 24 hours of the site visit.
Planning a renovation or extension?

Get a design for your own heritage home

Send us your plans, or book a site visit. Our in-house hydronic engineers will run the room-by-room heat-loss calculation, choose the right emitter for each zone and come back with a fixed-fee design and quote within 24 hours of the visit. Melbourne showroom: 43B Patch Circuit, Laverton North VIC 3026.

Reviews

Trusted by homeowners, builders and strata across Australia

★★★★★
Rated 5-star across NSW · ACT · VIC · QLD
★★★★★

"We've worked with AHHAC for 17 years now. They've installed and serviced our hot water plant across three commercial buildings. They pick up the phone on weekends — that's why we keep coming back."

James Holloway
Strata Manager · Melbourne CBD
Commercial hot water + heating service
★★★★★

"We commissioned AHHAC after another contractor abandoned the job halfway. They took over the design, fixed the existing issues, finished the install and gave us a five-year warranty. They saved the project."

Patricia Mendez
Architect · Carrum Downs, VIC
Project rescue — hydronic + cooling
★★★★★

"AHHAC delivered our 22-zone underfloor system on time, on budget and to spec. The crew were tidy, the documentation was thorough, and the commissioning was textbook. Couldn't ask for more from a trade partner."

David Chen
Custom Builder · Mosman, NSW
New build — 850m² residential
Last updated Content reviewed by the AHHAC Technical Team (NSW plumbing licence 262528C)Editorial standards
Call nowFree quote